Acti 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212  - Schneider Electric

Acti 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212 - Schneider Electric

₹ 4,247.68

₹ 5,012.26+18% GST

Freight Extra (Godown Delivery)

Seller SKU

PMI-0010

Quantity

Min 1 • Stock 100

Product Specification

Product NameActi 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212 - Schneider Electric
BrandSchneider Electric
Product CodePMI-0010
Country of ManufacturerIN
Weight210.000
CategoryRCCB & ELCB
Poles2P
Neutral PositionLeft
Network TypeAC
Earth Leakage Sensitivity30 mA
Earth Leakage Protection ClassType AC
Rated Breaking Capacity800 A conforming to EN/IEC 61008-1
Suitability For IsolationYes
Earth Leakage Protection Time DelayInstantaneous
Test CertificateYes
ModelA9N16212
Rated current80 A
Device short namexID

Product Description

Acti 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212 - Schneider Electric - Strategic Industrial Guidance

Acti 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212 - Schneider Electric

 

Complementary

Network frequency 50 Hz
[Ue] rated operational voltage 230...240 V AC 50 Hz
[Ui] rated insulation voltage 500 V AC 50 Hz
[Uimp] rated impulse withstand
voltage
6 kV
Contact position indicator Yes
Control type Toggle
Local signalling ON, OFF, fault trip
Mounting mode Clip-on
Mounting support DIN rail
Comb busbar and distribution
block compatibility
Downside: biconnect
Connection pitch 18 mm between phases
9 mm pitches 4
Height 81 mm
Width 36 mm
Depth 75 mm
Net weight 210 g
Colour White
Mechanical durability 4000 cycles
Electrical durability 4000 cycles
Locking options description Padlocking device
Connections - terminals Tunnel type terminals (top or bottom) 1…35 mm² rigid
Tunnel type terminals (top or bottom) 1…25 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom

 

Environment

Standards EN/IEC 61008-1
IEC 61008-2-1
EN 61008-2-1
Product certifications ISI
IP degree of protection IP20
Pollution degree 2
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Ambient air temperature for
operation
-5…40 °C
Ambient air temperature for
storage
-40…85 °C

 

Packing Units

Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 8 cm
Package 1 Width 4 cm
Package 1 Length 9 cm
Package 1 Weight 0.188 kg

 

Returns & Cancellation

Returns Policy:

1. Once orders are placed, cancellations are not permitted.

2. Payments for orders will not be adjusted or refunded in case of cancellation.

Shipping & Delivery Policy:

1. 100 INR will be charged as shipping fee if buyer and seller are from same city. If buyer and seller are from different cities, the shipping charges will be on "To Pay Basis" or at actuals.

2. Shipping freight costs will be additional and based on actuals, to be borne by the buyer.

3. Additional shipping services such as courier or door delivery will incur extra charges, to be borne by buyer on extra at actuals basis.

4. Material will be shipped exclusively on a To-Pay basis for Godown Delivery only.

Feedback

You're reviewing: Acti 9 80 A 2 Pole RCCB (Earth Leakage Sensitivity 30 mA), White, A9N16212 - Schneider Electric

Your Rating *

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.